Configuration of the ET 200SP
See the STEP 7 online help or the documentation of the configuration software
manufacturer.
Note
For I/O modules that are installed on a BaseUnit BU..D (light-colored BaseUnit), you always
have to set the parameter "Potential group" to "Enable new potential group". If you do not set
this parameter correctly, the CPU/interface module goes to STOP and generates a
parameter error.
Note
For PROFIBUS with configuration via GSD file
In the configuration software, you must set for the BU covers whether these are on a light-
colored or dark-colored BaseUnit.
Configuring F-modules with a GSD file
If you want to configure F-modules with a GSD file, you need S7-FCT in order to calculate
the F_iPar_CRC and assign the PROFIsafe addresses. Additional information can be found
on the Internet (https://support.industry.siemens.com/cs/ww/en/view/109763833).
You can find S7-FCT on the Internet
(https://support.industry.siemens.com/cs/ww/en/view/109762827).