Siemens SIMATIC ET 200SP System Manual page 69

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Installation
5.2 Installation conditions for motor starters
Designing interference-free motor starters
For interference-free operation of the ET 200SP station in accordance with standard
IEC 60947-4-2, use a dummy module before the first motor starter. No dummy module is
required to the right of the motor starter.
Note the following mounting rules:
Use the following dummy module on the standard mounting rail between the previous
module and the SIMATIC ET 200SP motor starter:
BU cover 15 mm: 6ES7133-6CV15-1AM0 with BaseUnit 6ES7193-6BP00-0BA0
For operation of the ET 200SP station with an unused BaseUnit, a cover must be provided
for the open BaseUnit plug contacts (power connector, power bus connector, and backplane
bus connector).
The cover protects the plug contacts against dirt. The BU cover can be ordered as an
accessory.
Mount the dummy module
The figure below provides a schematic representation of how to implement measures for
improving interference immunity.
68
Interface module
Digital input module
Digital output module
Dummy module
Motor starter
Motor starter
Motor starter
Server module
Infeed bus cover
System Manual, 09/2019, A5E03576849-AJ
Distributed I/O system

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents