Configuration control (option handling)
10.2 Creating the control data record
Control data record
For the configuration control of an ET 200SP CPU, you define a control data record 196
V2.0, which includes a slot assignment. The maximum slot of the configuration corresponds
to the slot of the server module or last slot of an ET 200AL I/O module (in a mixed
ET 200SP/ET 200AL configuration).
The table below shows the structure of a control data record with explanations of the
individual elements.
Table 10- 2
Configuration control: Structure of control data record 196
Byte
Element
0
Block length
1
Block ID
2
Version
3
Version
4
Slot 1 of the station master
5
Additional function for slot 1
6
Slot 2 of the station master
7
Additional function for slot 2
8
Slot 3 of the station master
9
Additional function for slot 3
:
:
4 + ((server module
Server module slot
slot - 1) × 2)
4 + ((server module
Additional function for server module slot
slot - 1) × 2) + 1
174
Code
4 + (maximum slot × 2)
196
2
0
Slot assignment 1 in the
station option
(always 1, because the
CPU is always in slot 1)
Slot assignment in the
station option
Slot assignment in the
station option
:
Server module slot as-
signment in the station
option*
Explanation
Header
Control element
Contains the information on which mod-
ule is inserted in which slot.
The value that you need to enter in the
corresponding byte depends on the fol-
lowing rule:
If the module exists in the station
•
option, enter the slot number of the
module.
If the module exists as empty slot
•
(with BU cover), enter the slot number
of the module + 128. (Example: mod-
ule as empty slot on slot 3: Enter 131
in the control element)
If the module does not exist in the
•
station option, enter 0.
Additional function
Contains information on whether a new
potential group will be opened in the
station option - by replacing a dark-
colored BaseUnit with a light-colored
BaseUnit.
If you replace a dark-colored Ba-
•
seUnit with a light-colored BaseUnit,
enter 1 as additional function.
If you accept the BaseUnit from the
•
station master, enter 0 as additional
function.
Distributed I/O system
System Manual, 09/2019, A5E03576849-AJ