Creating The Control Data Record; Introduction - Siemens SIMATIC ET 200SP System Manual

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

10.2

Creating the control data record

10.2.1

Introduction

Required steps
To create a control data record for the configuration control, follow these steps:
1. Create a PLC data type that contains the structure of the control data record.
The following figure shows a PLC data type "CTR_REC", which contains the structure of
the control data record for an ET 200SP interface module.
Figure 10-3
2. Create a global data block.
Distributed I/O system
System Manual, 09/2019, A5E03576849-AJ
Creating control data record 196 using an IM 155-6 PN HF as an example
Configuration control (option handling)
10.2 Creating the control data record
171