Wiring
6.8 Connecting cable shields for I/O modules
Required tools
● Stripping tool
Procedure
Watch the "Wiring BaseUnits" video sequence
(http://support.automation.siemens.com/WW/view/en/95886218)
To connect the cable shield, follow these steps:
1. If necessary, connect the supply voltage L+ and ground to the BaseUnit.
2. Press the shield contact up into the mount until you hear it click into place.
3. Remove the cable insulation material around the shield terminal.
Connect the cable to the BaseUnit and place the cable in the shield contact.
4. Insert the shield terminal into the shield contact.
5. Tighten the shield terminal with approximately 0.5 Nm.
①
②
③
④
Figure 6-7
104
Mount
Supply voltage L+, ground
Shield contact
Flat connector for push-on contacts
(6.3 × 0.8 mm)
Mounting the shield contact
⑤
Insulation material removed (approx. 20 mm)
⑥
Cable to the encoder
⑦
Shield terminal
System Manual, 09/2019, A5E03576849-AJ
Distributed I/O system