Troubleshooting For Cpu; Error Indicator On - Delta AH Series Operation Manual

Motion controller
Hide thumbs Also See for AH Series:
Table of Contents

Advertisement

AH Mo t io n C on tr o ll er – O per a ti o n M an u a l
Error code
16#A0FB
The transmission registers in AH10COPM-5A are full.
16#A0FC
9.3

Troubleshooting for CPU

You can get the corrective actions from the tables below according to the error codes.

9.3.1. ERROR Indicator ON

Error Code
16#000B
16#000D
16#0010
16#0011
16#0012
16#0014
16#0015
16#0016
16#0017
16#001B
_9
16#001C
9 - 3 6
The reception registers in AH10COPM-5A are full.
Description
The program in the PLC is damaged.
The CPU parameters are damaged.
The access to the memory in the
CPU is denied.
The PLC ID is incorrect. (SM9)
The PLC password is incorrect.
(SM9)
The procedure of restoring the
system can not be executed. (SM9)
The module table is incorrect.
(SM10)
The module setting is incorrect.
(SM10)
The data register exceeds the
device range. (SM10)
Timed interrupt 0 is set incorrectly.
Timed interrupt 1 is set incorrectly.
Description
Download the program again.
Reset the CPU parameter, and download it.
Download the program or parameters again. If the problem
still occurs, please contact the manufacturer.
Please check the PLC ID.
Please check the PLC password.
The contents of the system backup file are incorrect, or the
file does not exist in the path specified. If the file exists and
the procedure of restoring the system can not be executed,
please back up the system again. If the error still occurs,
please contact the manufacturer. (You can refer to AH
Motion Controller – Operation Manual for more details
about using memory cards)
The module table stored in the CPU module is incorrect.
Compare the module table in HWCONFIG with the actual
module configuration, and download the module table
again.
The module setting stored in the CPU module is incorrect.
Check whether the version of the module inserted in the slot
is the same as the version of the module in HWCONFIG.
After the version of the module is updated, users can
download the module setting again.
The data register stored in the CPU module exceeds the
device range. Check whether the module parameter in
HWCONFIG is correct, and download the module
parameter again.
Set the CPU parameter in HWCONFIG again, and
download the CPU parameter again.
Set the CPU parameter in HWCONFIG again, and
download the CPU parameter again.
LED indicator status
CPU
BUS FAULT
Blinking
Blinking
Corrective action
Module
ERROR
OFF
OFF