Latched Devices - Delta AH Series Operation Manual

Motion controller
Hide thumbs Also See for AH Series:
Table of Contents

Advertisement

AH Mo t io n C on tr o ll er – O p er a t io n M a nu a l

5.2.3. Latched Devices

Latched areas of each type of device
Device
X
Y
M*
SM
S
T*
C*
HC/AC*
D*
_5
SR
L
E
*Note: You can define the range of latched areas for T, C, M and D and set the devices to be non-latched. Note that the
range should not exceed the available device range, and only 32768 D devices at most can be non-latched. For example,
you can set D50~D32817 or D32768~D65535 to latched area though the default range of latched areas is D0~D32767.
Do not disconnect power or CPU module while the power is on. Once the PLC is disconnected from the backplane, the
data in the latched area such as devices will be affected.
5 - 4
Function
Device range
X devices (bit):
Input relay
X0.0~X511.15
X devices (word): X0~X511
Y devices (bit):
Output relay
Y0.0~Y511.15
Y devices (word): Y0~Y511
Auxiliary relay
M0~M8191
Special
SM: SM0~SM2047
auxiliary relay
Stepping relay
S0~S2047
Timer
T0~T2047
Counter
C0~C2047
HC: HC0~HC63
32-bit counter
AC: AC0~ AC55
(AHxxEMC)
D device (bit):
D0.0~D65535.15
Data register
D device (word):
D0~D65535
Special data
SR: SR0~SR2047
register
Link register
L0~ L65535
Index register
E0~E31
Latched area
All devices are non-latched.
All devices are non-latched.
Default: M0~M8191
Some devices are latched, and can not be
changed. Refer to the table of special auxiliary
relays in the appendices for more information.
All devices are non-latched.
Default: T0~T2047.
Default: C0~C2047.
Default: HC0~HC63.
AC devices are non-latched.
Default: D0~D32767.
At most 32768 devices can be latched devices.
Some are latched, and can not be changed.
Refer to the list of special data registers for more
information.
All devices are non-latched.
All devices are non-latched.