Auxiliary Relays (M); Special Auxiliary Relays (Sm/Am); Data Registers (D) - Delta AH Series Operation Manual

Motion controller
Hide thumbs Also See for AH Series:
Table of Contents

Advertisement

AH Mo t io n C on tr o ll er – O p er a t io n M a nu a l
transistors, and TRIACs (AC thyristors). Contact A or contact B of the output can be used several times in the program,
but the output should be used only once in the program. Otherwise, according the program-scanning principle of the
PLC, the state of the output depends on the circuit connected to the last output in the program.
 The output number (the decimal number)
For the PLC, the input numbers start from X0.0. The number of outputs varies with the number of outputs on the digital
input/output modules, and the outputs are numbered according to the order in which the digital input/output modules
are connected to the PLC. The maximum number of outputs on the PLC can reach up to 8192, and the range is
between Y0.0 and Y511.15.
The output which is not practically put to use can be used as a general device.
 The output type
The outputs are classified into two types.
1. Regenerated output: Not until the program executes the instruction END is the information fed out according to the
states of the outputs. For example, OUT Y0.0.
2. Direct output: When the instructions are executed, the information is fed out according to the states of the outputs.
For example, OUT DY0.0.

5.2.6. Auxiliary Relays (M)

The auxiliary relay has contact A and contact B. It can be used several times in the program. You can combine the control
loops by means of the auxiliary relay, but can not drive the external load by means of the auxiliary relay. The auxiliary
relays can be divided into two types according to their attributes.
1. For general use: If an electric power cut occurs when the PLC is running, the auxiliary relay for general use will be
reset to OFF. When the power supply is restored, the auxiliary relay for general use is still OFF.
_5
2. For latched use: If an electric power cut occurs when the PLC is running, the state of the auxiliary relay for latched use
will be retained. When the power supply is restored, the state remains the same as that before the electric power cut.
5.2.7. Special Auxiliary Relays (SM)
SM: special auxiliary relays
Every special auxiliary relay has its specific function. Please do not use the special auxiliary relays which are not defined.
For function descriptions of each special auxiliary relay (SM), refer to Appendix 1: Special Auxiliary Relays Table of AH
Motion Controller - Standard Instructions Manual.

5.2.8. Data Registers (D)

The data register stores the 16-bit data. The highest bit represents either a positive sign or a negative sign, and the values
which can be stored in the data registers range from -32,768 to +32,767. Two 16-bit registers can be combined into a
32-bit register, i.e. (D+1, D) in which the register whose number is smaller represents the low 16 bits. The highest bit
represents either a positive sign or a negative sign, and the values which can be stored in the data registers range from
-2,147,483,648 to +2,147,483,647. Besides, four 16-bit registers can be combined into a 64-bit register, i.e. (D+3, D+2,
D+1, D) in which the register whose number is smaller represents the lower 16 bits. The highest bit represents either a
positive sign or a negative sign, and the values which can be stored in the data registers range from
-9,223,372,036,854,776 to +9,223,372,036,854,775,807.
The registers can be classified into two types according to their properties:
5 - 6

Advertisement

Table of Contents
loading

Table of Contents