Applicable Wire Sizes

Table 2.7 shows the wire size of each terminal. Select an appropriate wire size considering the current capac-
ity.
Termi-
Terminal Type
nal
Code
Analog I/O ter-
L1 to
minals
L9
Sequence I/O
1 to 40
terminals
Control power
RC, SC,
supply input
TC
terminals
* Use shielded twisted-pair wires to input an external frequency reference.

Control Circuit Wiring Precautions

Observe the following precautions when wiring control circuits.
Separate the control circuit wirings from the analog I/O (Terminals L1 to L9) wirings, relay sequence I/O
(Terminals 1 to 40) wiring, other power lines and power supply lines.
Use shielded twisted-pair cables for analog I/Os (Terminals L1 to L9) to prevent malfunctions caused by
noise.
Lay the shielded wires so that they will not have contact with other signal lines and devices.
Tighten the screws with the specified tightening torque.
Use closed-loop crimp terminals to connect cables to the terminal block.
Use a Phillips screw driver to tighten terminal screws.
Table 2.7 Wire Sizes
Applicable
Termi-
Tightening
Wire Size
nal
Torque
2
Screw
(N·m)
mm
(AWG)
0.5 to 2
M3.5
0.8 to 1.0
(20 to 14)
0.5 to 2
M3.5
0.8 to 1.0
(20 to 14)
8 to 14
M5
2 to 2.5
(8 to 6)
Wiring Control Circuit Terminals
Recom-
mended
Wire Type
Wire Size
(For reference)
2
mm
(AWG)
1.25
• Shielded twisted-pair wire
(12)
1.25
• Insulated vinyl sheathed cable
(12)
(CVV) for control circuit
8
• 600-V vinyl insulated, vinyl
(8)
sheathed cable (VV)
*