Operation Errors - YASKAWA FSDrive-MV1S Instructions Manual

Super energy-saving medium-voltage inverter
Table of Contents

Advertisement

Operation Errors

An operation error will occur if there is an invalid setting or a contradiction between two constant settings. It
won't be possible to start the Inverter until the constants have been set correctly. (The alarm output and fault
contact outputs will not operate either.)
When an operation error has occurred, refer to the following table to identify and correct the cause of the
errors.
Display
Meaning
OPE02
Constant Setting Range
Limit
Error
OPE03
Multi-function Input
Selection Error
Terminal
OPE07
Multi-function Analog
Analog
Input Selection Error
Selection
OPE08
Constant Selection
Ctrl Func
Error
Error
OPE10
V/f Data Setting Error
V/f Ptrn Set-
ting
OPE11
Carr Freq/
Constant Setting Error
On-Delay
ERR
EEPROM Write Error
EEPROM
R/W Err
Table 7.3 Operation Error Displays and Incorrect Settings
The constant setting is outside of the valid setting range. Press the ENTER Key on
the Digital Operator to display OPE fault constant (U1-34).
One of the following errors has been made in the multi-function input (H1-01 to H1-
10) settings:
• The same setting has been selected for two or more multi-function inputs.
• An up or down command was selected independently. (They must be used
together.)
• The up/down commands (10 and 11) and Accel/Decel Ramp Hold (A) were
selected at the same time.
• Speed Search 1 (61, maximum output frequency) and Speed Search 2 (62. set fre-
quency) were selected at the same time.
• The up/down commands (10 and 11) were selected while PID Control Method
Selection (b5-01) was enabled.
• Positive and negative speed commands have not been set at the same time.
• The emergency Stop Command NO and NC have been set at the same time.
The same setting has been selected for two or more multi-function analog inputs.
A setting has been made that is not required in the current control method. Ex.: A
function used only with open-loop vector control was selected for flux vector con-
trol. Press the ENTER Key on the Digital Operator to display OPE fault constant
(U1-34).
Constants E1-04, E1-06, E1-07, and E1-09 do not satisfy the following conditions:
• E1-04 (FMAX) ≥ E1-06 (FA) > E1-07 (FB) ≥ E1-09 (FMIN)
The motor overload detection start level (L1-06) has been set to a value above the
motor overload detection level (L1-07).
A verification error occurred when writing EEPROM.
• Try turning the power supply off and on again.
• Try setting the constants again.
Protective and Diagnostic Functions
Incorrect settings
9
7-

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents