YASKAWA FSDrive-MV1S Instructions Manual page 98

Super energy-saving medium-voltage inverter
Table of Contents

Advertisement

Multi-function Analog Outputs: H4
User constants for multi-function analog outputs are shown in the following table.
Name
Constant
Number
Display
Monitor selection
(terminal AO1)
H4-01
Term AO1 Signal
Gain (terminal AO1)
H4-02
Term AO1 Gain
Bias (terminal AO1)
H4-03
Term AO1 Bias
Monitor selection
(terminal AO2)
H4-04
Term AO2 Signal
Gain (terminal AO2)
H4-05
Term AO2 Gain
Bias (terminal AO2)
H4-06
Term AO2 Bias
Monitor selection
(terminal AO3)
H4-07
Term AO3 Signal
Gain (terminal AO3)
H4-08
Term AO3 Gain
Setting
Description
Range
Sets the number of the monitor
item to be output (U1-
)
0 to 99
from terminal AO1.
Sets the multi-function analog
output 1 voltage level gain.
Sets whether the monitor item
output will be output in multi-
ples of 10 V.
30.00
The maximum output from the
terminal is 10 V. A meter cali-
bration function is available.
Sets the multi-function analog
output 1 voltage level bias.
Sets output characteristic up/
-100.0
down parallel movement as a
percentage of 10 V.
100.0
The maximum output from the
terminal is 10 V. A meter cali-
bration function is available.
Sets the number of the monitor
item to be output (U1-
)
0 to 99
from terminal AO2.
Sets the multi-function analog
output 2 voltage level gain.
Sets whether the monitor item
output will be output in multi-
ples of 10 V.
30.00
The maximum output from the
terminal is 10 V. A meter cali-
bration function is available.
Sets the multi-function analog
output 2 voltage level bias.
Sets output characteristic up/
-100.0
down parallel movement as a
percentage of 10 V.
100.0
The maximum output from the
terminal is 10 V. A meter cali-
bration function is available.
Sets the number of the monitor
item to be output (U1-
)
0 or 99
from terminal AO3.
Sets the multi-function analog
output 3 voltage level gain.
Sets whether the monitor item
output will be output in multi-
ples of 10 V.
30.00
The maximum output from the
terminal is 10 V. A meter cali-
bration function is available.
User Constant Tables
Change
Methods
Factory
during
Open-
Setting
Operation
loop
Vector
2
Yes
A
0 to
1.00
Yes
A
to
0.0%
Yes
A
3
Yes
A
0 to
1.00
Yes
A
to
0.0%
Yes
A
5
Yes
A
0 to
1.00
Yes
A
Control
MEMOBUS
Register
Flux
Vector
A
470H
A
471H
A
472H
A
473H
A
474H
A
475H
A
476H
A
477H
33
5-