Run Command

This section explains input methods for the Run Command.

Selecting the Run Command Source

Set constant b1-02 to select the source for the Run Command.
Related Constants
Constant
Number
b1-02
Performing Operations Using a Digital Operator
When b1-02 is set to 0, you can perform Inverter operations using the Digital Operator keys (RUN, STOP,
JOG, and FWD/REV). For details on the Digital Operator, refer to Chapter 3 Digital Operator and Modes.
Performing Operations Using Control Circuit Terminals
When b1-02 is set to 1, you can perform Inverter operations using the control circuit terminals.
-4
6
Name
Description
Display
Operation method
Set the Run Command input
selection
method.
0: Digital Operator
1: Control circuit terminal
(sequence input)
Run Source
2: MEMOBUS communica-
tions
3: PLC
Change
Setting
Factory
during
Open-
Range
Setting
Operation
loop
Vector
0 to 3
3
No
Control
Methods
MEMOBUS
Register
Flux
Vector
Q
Q
1A1H