Input Terminal Functions

This section explains input terminal functions, which set operating methods by switching functions for the
multi-function contact input terminals (S3 to S12).
Temporarily Switching Operation between Digital Operator and Control
Circuit Terminals
You can switch the Inverter Run Command inputs and frequency reference inputs between local (i.e., Digital
Operator) and remote (input method using b1-01 and b1-02).
You can switch between local and remote by turning on and off the terminals if an output from H1-03 to H1-
16 (multi-function contact input terminal S3 to S16 function selection) has been set to 1 (local/remote selec-
tion).
To set the control circuit terminals to remote, set b1-01 and b1-02 to 1 (Control circuit terminals).
The control circuit terminals are normally used via PLC, so set b1-01 and b1-02 to 3(PLC) and do not change
this setting.
Related Constants
Name
Constant
Number
Display
Reference selection
b1-01
Reference Source
Operation method
selection
b1-02
Run Source
You can also perform local/remote switching using the LOCAL/REMOTE Key on the Digital Operator. When
the local/remote function has been set in the external terminals, the LOCAL/REMOTE Key function on the
Digital Operator will be disabled.
INFO
Setting
Description
Range
Set the frequency reference
input method.
0: Digital Operator
1: Control circuit terminal
0 to 3
(analog input)
2: MEMOBUS communica-
tions
3: PLC
Set the Run Command input
method.
0: Digital Operator
1: Control circuit terminal
0 to 3
(sequence input)
2: MEMOBUS communica-
tions
3: PLC

Input Terminal Functions

Control
Change
Methods
Factory
during
Open-
Setting
Flux
Operation
loop
Vector
Vector
3
No
Q
Q
3
No
Q
Q
MEMOBUS
Register
1A0H
1A1H
43
6-