Autotuning Constants: C

The following settings are made with the autotuning constants (C constants): Acceleration/deceleration times,
s-curve characteristics, slip compensation, torque compensation, and speed control.
Acceleration/Deceleration: C1
User constants for acceleration and deceleration times are shown in the following table.
Name
Constant
Number
Display
Acceleration time 1
C1-01
Accel Time 1
Deceleration time 1
C1-02
Decel Time 1
Acceleration time 2
C1-03
Accel Time 2
Deceleration time 2
C1-04
Decel Time 2
Acceleration time 3
C1-05
Accel Time 3
Deceleration time 3
C1-06
Decel Time 3
Acceleration time 4
C1-07
Accel Time 4
Deceleration time 4
C1-08
Decel Time 4
Emergency stop time
C1-09
Fast Stop Time
Accel/decel time
switching frequency
C1-11
Acc/Dec SW Freq
Setting
Description
Range
Sets the acceleration time to
accelerate from 0 to the maxi-
mum output frequency, in 1-
second units.
Sets the deceleration time to
decelerate from the maximum
output frequency to 0, in 1-sec-
ond units.
The acceleration time when the
multi-function input "accel/
decel time 1" is set to on.
The deceleration time when the
multi-function input "accel/
decel time 1" is set to on.
The acceleration time when the
multi-function input "accel/
decel time 2" is set to on.
0.0 to
6000.0
The deceleration time when the
multi-function input "accel/
decel time 2" is set to on.
The acceleration time when the
multi-function input "accel/
decel time 1" and "accel/decel
time 2" are set to on.
The deceleration time when the
multi-function input "accel/
decel time 1" and "accel/decel
time 2" are set to on.
The deceleration time when the
multi-function input "Emer-
gency (fast) stop" is set to on.
This function can be used as a
stopping method when a fault
has been detected.
Sets the frequency for auto-
matic acceleration/deceleration
switching.
Below set frequency: Accel/
decel time 4
0.0 to
Above set frequency: Accel/
100.00
decel time 1
The multi-function input
"accel/decel time 1" or "accel/
decel time 2" take priority.
User Constant Tables
Control
Change
Methods
Factory
during
Open-
Setting
Flux
Operation
loop
Vector
Vector
60.0 s
Yes
Q
Q
120.0 s
Yes
Q
Q
60.0 s
Yes
A
A
120.0 s
Yes
A
A
60.0 s
No
A
A
120.0 s
No
A
A
60.0 s
No
A
A
120.0 s
No
A
A
10.0 s
No
A
A
0.00%
No
A
A
MEMOBUS
Register
240H
241H
242H
243H
244H
245H
246H
247H
248H
24AH
13
5-