Operation Avoiding Resonance (Jump Frequency Function)

The jump frequency function operates the motor while avoiding resonance caused by characteristic frequen-
cies in the machinery.
This function is effective in creating a frequency reference dead band.
During constant-speed operation, operation within the jump frequency range is prohibited. Smooth operation
still used during acceleration and deceleration, i.e., jumps are not performed.
Related Constants
Constant
Number
d3-01
d3-02
d3-03
d3-04
The relationship between the output frequency and the jump frequency reference is as follows:
-16
6
Name
Description
Display
Signal level selection
0: 0 to 10V
(terminal AI4)
1: -10V to 10V
Term AI4 Signal
Multi-function analog
input
Select multi-function analog
(terminal AI4)
input function for terminal AI4.
Term AI4 Sel
Gain (terminal AI4)
Sets the input gain (level) when
terminal AI3 is 10 V. Set
according to the 100% value
Term AI4 Gain
selected in H3-13.
Bias (terminal AI4)
Sets the input gain (level) when
terminal AI3 is 0 V. Set accord-
ing to the 100% value selected
Term AI4 Bias
in H3-13.
Analog input filter
Sets primary delay filter time
time constant
constant in seconds for the four
analog input terminal
(AI1,AI2,AI3,AI4).
Filter Avg Time
Effective for noise control etc.
Name
Description
Display
Jump frequency 1
Set the center values of the
jump frequencies in %.
Jump Freq 1
This function is disabled by set-
Jump frequency 2
ting the jump frequency to 0
Hz. Always ensure that the fol-
Jump Freq 2
lowing applies:
Jump frequency 3
d3-01 ≥ d3-02 ≥ d3-03
Operation in the jump fre-
quency range is prohibited but
Jump Freq 3
during acceleration and decel-
eration, speed changes
smoothly without jump.
Jump frequency width Sets the jump frequency band-
width in %.
The jump frequency will be the
Jump Bandwidth
jump frequency ± d3-04.
Change
Setting
Factory
during
Open-
Range
Setting
Operation
loop
Vector
0 or 1
0
No
00 to
0FH
No
1FH
0.0 to
100.0%
Yes
1000.0
-100.0
to
0.0%
Yes
100.0
0.00 to
0.00
No
2.00
s
Change
Setting
Factory
during
Open-
Range
Setting
Operation
loop
Vector
0.0 to
0.0%
No
100.0
0.0 to
0.0%
No
100.0
0.0 to
0.0%
No
100.0
0.0 to
1.0%
No
100.0
Control
Methods
MEMOBUS
Register
Flux
Vector
A
A
45BH
A
A
45CH
A
A
45DH
A
A
45EH
A
A
45FH
Control
Methods
MEMOBUS
Register
Flux
Vector
A
A
2F0H
A
A
2F1H
A
A
2F2H
A
A
2F3H

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents