Selecting Analog Monitor Items
The digital operator monitor items (U1-
terminals AO1 to AO4. Refer to Chapter 5 User Constants, and set the values for the
(status monitor).
Adjusting the Analog Monitor Items
Adjust the output voltage for multi-function analog output terminals AO1 to AO4 using the gain and bias in
H4-02, H4-03, H4-05, H4-06, H4-08, H4-09, H4-11, and H4-12.
Adjusting the Meter
The output voltage for terminals AO1 to AO4 can be adjusted while the Inverter is stopped. For example, just
pressing the Enter Key and displaying the data setting display for H4-02 or H4-03 will cause the following
voltage to be output by the AO1 terminals.
10 V/100% monitor output × output gain (H4-02) + output bias (H4-03)
Gain x 10 V
Switching Analog Monitor Signal Levels
Monitor items corresponding to -10 to 10 V output 0 to 10 V signals when the monitor value is positive (+),
and 0 to -10 V signals when the monitor value is negative (-). For monitor items corresponding to -10 to 10 V,
refer to Chapter 5 User Constants.
[status monitor]) are output from multi-function analog output
Output voltage
Bias x 10/100 V
Fig 6.25 Monitor Output Adjustment
Monitor Constants
part of U1-
Monitor item
53
6-