User constants for torque limits are shown in the following table.
Constant
Number
L7-01
L7-02
L7-03
L7-04
Note The forward torque limit is the limit value when the analog input signal generates forward torque. This torque limit setting is enabled even when the
analog input signal generates forward torque while the motor is operating (regeneration).
* The factory setting will change when the control method is changed.
-42
5
Name
Description
Display
Overtorque/Under-
torque
detection selection 2
Multi-function output for over-
torque detection 1 is output to
Torq Det 2 Sel
multi-function contact output
when overtorque detection 1
Overtorque/Under-
NO or overtorque detection 1
torque
NC is selected. Multi-function
detection level 2
output for overtorque detection
Torq Det 2 Lvl
2 is output to multi-function
contact output when overtorque
Overtorque/Under-
detection 2 NO or overtorque
torque
detection 2 NC is selected.
detection time 2
Torq Det 2 Time
Name
Description
Display
Forward drive
torque limit
Torq Limit Fwd
Sets the torque limit value as a percentage
of the motor rated torque.
Reverse drive
Four individual regions can be set.
torque limit
Output frequency
Torq Limit Rev
Upper limit
Accelerates to
lower limit
Forward
regenerative
Lower limit
torque limit
Forward
operation/stop
Torq Lmt Fwd
On
UP command
On
Rgn
DOWN
command
On
Frequency
Reverse
matching signal*
Power supply
regenerative
* The frequency matching signal turns on when the motor
is not accelerating/decelerating while the Run Command is on.