Reference Detection: L4
User constants for the reference detection function are shown in the following table.
Constant
Number
L4-01
L4-02
L4-03
L4-04
L4-05
-40
5
Name
Description
Display
Speed agree detection
Effective when "Desired fre-
level
quency (ref/setting) agree 1,"
"Frequency detection 1," or
"Frequency detection 2" is set
for a multi-function output.
Spd Agree Level
Frequencies to be detected are
set as a percentage.
Speed agree detection
Effective when "Frequency
width
(speed) agree 1," "Desired fre-
quency (speed) agree 1," or
"Frequency (FOUT) detection
1," Frequency (FOUT) detec-
tion 2 is set for a multi-function
Spd Agree Width
output.
Sets the frequency detection
width as a percentage.
Speed agree detection
Effective when "Desired fre-
level (+/-)
quency (speed) agree 2," "Fre-
quency (FOUT) detection 3,"
or "Frequency (FOUT) detec-
tion 4" is set for a multi-func-
Spd Agree Lvl+-
tion output.
Frequency detection width is
set as a percentage.
Speed agree detection
Effective when "Frequency
width (+/-)
(speed) agree 2," "Desired fre-
quency (speed) agree 2," Fre-
quency (FOUT) detection 3 or
"Frequency detection 4" is set
Spd Agree Width+-
for a multi-function output.
Frequency detection width is
set as a percentage.
Operation when
0: Stop (Operation follows the
frequency reference is
frequency reference.)
missing
1: Operation at 80% speed
continues. (At 80% of speed
before the frequency
reference was lost)
Ref Loss Sel
Frequency reference is lost:
Frequency reference dropped
over 90% in 400 ms.
Change
Setting
Factory
during
Open-
Range
Setting
Operation
loop
Vector
0.0 to
0.0%
No
100.0
0.0 to
2.0%
No
100.0
-100.0
to
0.0%
No
100.0
0.0 to
2.0%
No
100.0
0 or 1
0
No
Control
Methods
MEMOBUS
Register
Flux
Vector
A
A
530H
A
A
531H
A
A
532H
A
A
533H
A
A
534H