YASKAWA FSDrive-MV1S Instructions Manual page 65

Super energy-saving medium-voltage inverter
Table of Contents

Advertisement

The constant settings that indirectly change control performance are listed below.
Acceleration/deceleration time (C1-01 to -11) Adjusts the torque during acceleration and deceleration.
S-curve characteristics (C2-01 to -04)
Jump frequency (d3-01 to -04)
Analog input filter time constant (H3-16)
Stall prevention (L3-01 to -03)
Torque limit (L7-01 to -04)
-10
4
Table 4.4 Constants that Indirectly Change Control Performance and their Functions
Name (Constant No.)
Functions
Used to prevent shock at completion of acceleration/deceleration.
Used to avoid machine resonance points during operation.
Used to prevent fluctuation of analog input signals caused by noise.
Used to prevent motor stall or overvoltage (OV) for heavy-load operation
or rapid acceleration.
Factory setting: Disabled
Sets the maximum torque for vector control. When increasing the setting,
use an Inverter with higher capacity than the motor. Excessively decreas-
ing the setting under heavy load will cause motor stall.