Multi-function Contact Input Functions
Setting
Value
00
3-wire sequences (Forward/Reverse Run Command)
01
Local/Remote selection (on: Operator, off: Constant setting)
02
Option/Inverter selection (on: Option board)
Multi-step speed reference 1
03
When H3-09 (Multi-function analog input function selection) is set to 0 [Auxiliary frequency
(speed) reference], this function is combined with the master/auxiliary speed switch.
04
Multi-step reference 2
05
Multi-step reference 3
06
Jog frequency command (higher priority than multi-step speed reference)
07
Accel/decel time 1
08
External baseblock NO (NO contact: Baseblock at on)
09
External baseblock NC (NC contact: Baseblock at off)
0A
Acceleration/deceleration ramp hold (on: Acceleration/deceleration stopped, frequency on hold)
0B
OH2 alarm signal input (on: OH2 will be displayed)
0C
Multi-function analog input selection (on: Enable)
0E
Speed control integral reset (on: Integral control disabled)
0F
Not used (Set when the terminal is used for the built-in PLC or not used.)
10
Up command (Always set with the down command.)
11
Down command (Always set with the up command.)
12
FJOG command (on: Forward run at jog frequency (d1-17))
13
RJOG command (on: Reverse run at jog frequency (d1-17))
14
Fault reset (Reset when turned on.)
Timer function input [Functions are set in B4-01 and B4-02. Set with timer function output
18
(multi-function output).]
1A
Accel/decel time 2
Constants write enable (on: All constants can be written-in. off: All constants other than speed
1B
monitor are write prohibited.)
1E
Analog frequency reference sample/hold
1F
Frequency reference terminal AI0/AI1 selection (on: AI1)
External fault (Desired settings possible) Input mode: NO contact/NC contact, Detection mode:
20 to 2F
Normal/during operation, Stopping method: Deceleration to a stop/coast to a stop/ emergency
stop/ continues running
60
DC injection braking command (on: Performs DC injection braking)
61
External speed search command 1 (on: Speed search from maximum output frequency)
62
External speed search command 2 (on: Speed search from set frequency)
6F
Emergency stop (NO contact: Coast to a stop when on)
70
Emergency stop (NC contact: Coast to a stop when off)
71
Speed/torque control change (on: Torque control)
Speed control (ASR) proportional gain switch (on: C5-03, off: Gain determined by C5-01, C5-
77
03, and C5-09)
Note Set to 0F when contact input is used for the built-in PLC or not used as multi-function contact input.
Function
User Constant Tables
Control Methods
Open-
Flux
loop
Vector
Vector
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
No
Yes
Yes
Yes
Yes
No
Yes
No
Yes
5-
27

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents