Maintenance
9.5 Repair
Removing the module
1. Loosen the screws connecting the central brace with the frame of the cabinet, and remove
2. Close the inlet non-return valve
206
the central brace.
Figure 9-25
Diode module: water connection
supply and outlet pipes
water from the diode module.
Figure 9-26
Diode module: phase connections
and the outlet non-return valve
. Capture the cooling water using the catchment tray. Remove all
SINAMICS GM150 6SL3835-2LN44-2AA0
Operating Instructions Rev.201910281250 MUSTER
. Unscrew the water