3.6 Description of options
3.6.32

Suitability for marine use (option M66)

The converter design corresponds to the requirements of the following classification societies.
● Lloyds Register
● American Bureau of Shipping
● Germanischer Lloyd
● Bureau Veritas
● Det Norske Veritas
● Chinese Classification Society
The converter has the following supplementary equipment:
● Salt water resistant paint
● Strengthened mechanical cabinet design
● Handrail below the operator panel
● Mechanical cabinet door locking
● IP44 degree of protection
● Anti-condensation heating
The converter can be welded to the ship's hull plate
3.6.33

Controlled outgoing circuit for auxiliary equipment 400 V 3 AC (option N30)

This option includes a controlled outgoing feeder for external auxiliaries (3 AC 400 V, max.
4 KW). The controlled outgoing feeder is protected by a circuit breaker. The circuit breaker
setting range is cos phi = 0.8 (7 A up to 10 A).
The option can be used to operate external fans on motors and pumps and oil supply units. The
"ON" command at the drive closes the contactor. The "OFF" command opens the contactor.
Externally provide the necessary drive power supply. The terminal assignment is provided in
the circuit diagram of the drive.