Sine-Wave Filter (Option Y15); Table 3-3 Max. Permissible Cable Lengths; Figure 3-12 Connecting The Motor To The Sine-Wave Filter - Siemens Sinamics GM150 6SL3835-2LN44-2AA0 Operating And Installation Instructions

Medium-voltage drive
Table of Contents

Advertisement

3.6.34

Sine-wave filter (option Y15)

This option allows line motors or motors with insulation systems that are not compatible with
drives to be operated with speed control. The sine-wave filter supplies the motors with virtually
sinusoidal motor currents and voltages, which means that line motors can be used. Standard
cables (without EMC shielding) can also be used between the sine-wave filter and the motor.
When sine-wave filters are used, the voltage harmonic distortion at an output frequency of 50
Hz is less than 5%. When the sine-wave filter is used, refer to the performance data (see the
technical specifications). Only work machines with square load characteristic curve (centrifugal
pumps and water turbines) can be operated. Field-weakening operation is not permitted.
Possible rated output frequencies are limited to a range of 30 Hz to max. 66 Hz. The frequency
setting range is 1:10.
Table 3-3
Permissible maximum cable lengths (shielded and unshielded cables)
Without sine-wave filter
100 m
Connecting the motor to the sine-wave filter
A
B
C
Figure 3-12
SINAMICS GM150 6SL3835-2LN44-2AA0
Operating Instructions Rev.201910281250 MUSTER
Max. permissible cable lengths
Basic configuration
Parallel connection
Parallel connection, two separate winding systems
Connecting the motor to the sine-wave filter
3.6 Description of options
With sine-wave filter
1000 m
Description
59