Operation

8.5 Functions

8.5
Functions
8.5.1

Setpoint channel and closed-loop control

8.5.1.1

Setpoint channel

Setpoint addition
Fine tuning (correction variable) often needs to be carried out on site for applications in which
the command variables are generated by central control systems.
You achieve the correction variable using the addition point for the main and additional setpoint
in the setpoint channel. Both variables are imported simultaneously via two separate or one
setpoint source and added in the setpoint channel.
Adjustable parameters
Parameter
p1070
p1071
r1073
p1075
p1076
r1077
r1078
These parameters concern connector inputs to which the setpoint values are connected.
Function diagram
FP 3030
Direction reversal
A reversal of the rotational direction is necessary under the following conditions:
● When the drive should be operated in both directions of rotation.
● If the cables were connected with an incorrect phase sequence.
Note
Note that only one direction of rotation is enabled in the factory setting.
144
Setting
Main setpoint
Main setpoint scaling
Main setpoint effective
Supplementary setpoint
Supplementary setpoint scaling
Supplementary setpoint effective
Total setpoint effective
SINAMICS GM150 6SL3835-2LN44-2AA0
Operating Instructions Rev.201910281250 MUSTER