Ptx10003 Ac/Hvdc Power Specifications; Ptx10003 Ac Power Cord Specifications - Juniper PTX10003-80C Hardware Manual

Fixed packet transport router
Hide thumbs Also See for PTX10003-80C:
Table of Contents

Advertisement

System:
Zone 0:
Capacity:
Allocated power:
Actual usage:
Total system capacity: 6000 W (maximum 6000 W)
Total remaining power: 3193 W

PTX10003 AC/HVDC Power Specifications

The PTX10003 operates within the AC/HVDC input voltage range listed in
Table 16: PTX10003 AC/HVDC Power Specifications
Parameter
Input voltage (AC)
Input voltage (HVDC)
AC input line frequency

PTX10003 AC Power Cord Specifications

Detachable AC power cords are shipped with the chassis if you include them as part of your order. The
plug at the male end of the power cord fits into the power source outlet that is standard for your
geographical location.
NOTE:
In North America, AC power cords must not exceed 14.75 feet (approximately 4.5 meters)
in length, to comply with National Electrical Code (NEC) Sections 400-8 (NFPA 75, 5-2.2) and
210-52 and Canadian Electrical Code (CEC) Section 4-010(3). The cords that can be ordered for
the PTX10003 are in compliance.
Table 17 on page 57
lists AC power cord specifications provided for each country or region.
6000 W (maximum 6000 W)
2807 W (3193 W remaining)
1495 W
Minimum
180 VAC
190 VDC
47 Hz
Table 16 on page
Rated
200—277 VAC
240—380 VDC
50—60 Hz
56.
Maximum
305 VAC
400 VDC
63 Hz
56

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ptx10003-160c

Table of Contents