Procedure
1. In the "Interface selection - D410" dialog box, select the entry "Ethernet PNxIO (X200)" as
2. Select the interface parameter assignment that you would like to use to go online, and
The dialog box is closed, the SIMOTION D410 is created in the project navigator, and HW
Config is opened automatically (if parameterized).
An Ethernet subnet is created automatically.
The PG/PC is now connected to the SIMOTION D410 via Ethernet. You can configure and
parameterize your system.
Note
Please make sure that the PG/PC and SIMOTION D410 are located in the same subnet and
that S7 online access has been activated (PG/PC connection must be yellow and bold in
NetPro).
Inserting a further SIMOTION device
If you insert a further SIMOTION device using "Insert SIMOTION device", the PG/PC interface
selection dialog box is not displayed. The second SIMOTION device is automatically
connected to the PG/PC via Ethernet and a new unique IP address (last digit + 1 up to 255)
is calculated.
SIMOTION D410
Commissioning Manual, 04/2014
the interface selection.
Figure 4-4
Selecting the Ethernet interface
confirm with "OK".
Parameter assignment / addressing
4.2 Creating a project and configuring the communication
59