Procedure
Proceed as follows to configure the PROFIBUS DP interface:
1. In the "Interface Selection - D410" dialog box, select the entry "PROFIBUS DP/MPI (X21)"
2. Select the interface parameter assignment that you would like to use to go online, and
The dialog box is closed, the SIMOTION D410 is created in the project navigator, and HW
Config is opened automatically (if parameterized). A PROFIBUS subnet with factory settings
(1.5 Mbps transmission rate) is created automatically.
The PG/PC is now connected to the SIMOTION D410 via PROFIBUS. You can configure and
parameterize your system
Note
If you do not use the factory settings, you must configure the PROFIBUS interfaces in HW
Config.
The active state setting of the connection to the PG/PC is visualized only in NetPro!
Inserting a further SIMOTION device
If you insert a further SIMOTION device using "Insert SIMOTION device", the PG/PC interface
selection dialog box is not displayed. Any further SIMOTION device is automatically connected
to the PG/PC via PROFIBUS and a new unique DP address (address 4, 5 ... up to 125) is
calculated.
SIMOTION D410
Commissioning Manual, 04/2014
as the interface selection.
Figure 4-3
Selecting a PROFIBUS interface
confirm with "OK".
Parameter assignment / addressing
4.2 Creating a project and configuring the communication
57