Commissioning (software)
5.16 Deleting data
Memory reset with the mode switch
The mode switch function is implemented in SIMOTION D410 by means of a DIL switch
(DIL = Dual-In-Line). Use this DIL switch (switch S1 - S3) to set the binary code for the mode
of operation.
Information pertaining to to the switch positions and corresponding modes of operation is
available in the
You can only reset memory using the mode switch if SIMOTION D410 is operating in offline
mode.
Proceed as follows to reset the memory:
1. Select the MRES operating mode by
2. Set switch 1 to ON (STOP mode) once the RUN/STOP LED permanently lights up yellow.
3. Within 3 seconds, set the switch back to MRES operating mode by setting switch S1 to
4. Wait until the D410 has completed the memory reset (RUN/STOP LED permanently lights
5. Now set the mode switch back to the required operating mode; for example, set switches
154
SIMOTION D410 Manual.
– Setting mode switches S1 to S3 to OFF AND
– Using the service selector switch to ensure that no service functions are selected (S4
to S7 = OFF).
The RUN/STOP LED will begin flashing soon after this (slowly flashing yellow).
Figure 5-41
MRES switch position
OFF again. The memory reset is performed (the RUN/STOP LED flashes yellow quickly).
up yellow).
S1, S2, and S3 to ON for RUN mode.
Note
Memory reset is canceled if you do not return the DIL switch to MRES as specified within
3 seconds. Repeat the procedure in this case.
SIMOTION D410
Commissioning Manual, 04/2014