Table 5-5
Explanation of the figure
No.
Meaning
Selection of a telegram
● The drive telegrams (telegrams 1 ... 6 and telegram 1xx) are defined in accordance with the PROFIdrive
specification and can be selected based on the required functional scope.
● You can transfer the signals of the I/Os or the global measuring inputs, for example, via the telegrams 39x.
Telegram 39x is also required for the time synchronization between SIMOTION and SINAMICS.
● Free telegram configuration with BICO allows you to define your own telegram.
● Free telegram configuration with p0915/p0916 (for TM15/17).
● Telegrams 37x for activation of the infeed (relevant only to SIMOTION D4x5/D4x5-2).
The "Standard/automatic" and "User-defined" settings are only visible if "Use symbolic assignment" is activated. Using
the setting "Standard/automatic" is generally recommended.
The "User-defined" setting allows the automatic telegram setting, telegram extension, and address adaptation to be
deactivated or activated.
● "Automatic PROFIdrive telegram setting" allows the telegram to be set by the system depending on the configured
technology (telegram selection, e.g. for infeed, drive, and control unit incl. onboard I/O).
● "Automatic telegram extension" allows the telegram to be extended by the system depending on the configured
technology (e.g. if the technology data block is activated in the axis configuration).
● "Permit automatic address adaptation" allows addresses to be adapted by the system in the case of address
offsets, for example. Address offsets can occur, for example, if a telegram is extended and the adjacent addresses
are already occupied by other telegrams.
With TM15/TM17 High Feature, "Automatic PROFIdrive telegram setting", "Automatic telegram extension", and
"Automatic address adaptation" cannot be deactivated by design, since for these drive objects the telegram is always
set up in accordance with the parameterized terminal functionality (DI, DO, output cam, measuring input) and cannot
be extended.
"Automatic PROFIdrive telegram setting" and "Automatic telegram extension" must be deactivated if the telegrams
are to be configured manually for TM15 DI/DO, TM31, and TB30 and interconnected with BICO.
See Section Setting up communication for symbolic assignment (Page 121).
Telegram status
(Meaning of the symbols, see table below)
Length: Displays the size of the telegram component.
Address: Addresses in HW Config The addresses will be displayed only if the addresses have been defined.
Displays the SIMOTION object that is interconnected to the SINAMICS object (e.g. axis or encoder).
Changing the telegram sequence
Before the alignment, all drive objects without input/output addresses ("---..---") must be moved behind the objects
with valid input/output addresses or those still to be aligned ("???..???").
"Manual" adaptation of the telegram configuration (e.g. when additional data, such as a motor temperature, is to be
transferred via the telegram).
Display of the individual control and status words of the associated telegram.
Setting up the addresses (alignment of the addresses with HW Config)
Only the addresses for the respective drive unit are determined (no automatic determination of telegrams / BICO
interconnections).
SIMOTION D410
Commissioning Manual, 04/2014
Commissioning (software)
5.7 Setting up addresses and message frames
123