Service selector switch
To back up diagnostic data and non-volatile SIMOTION data using a service selector switch,
proceed as follows:
1. Set the service selector switch to the "Diagnostics" setting (i.e. set DIP switch S7 to ON).
Figure 7-2
Writing diagnostic data using a switch position
2. The diagnostic data and non-volatile SIMOTION data are backed up to the CF card.
3. Once the backup is complete, switch off the SIMOTION D410.
4. Remove the CF card and reset the service selector switch to its original setting.
7.2.2.4

Procedure for backing up during startup

Procedure
Backing up diagnostic data and non-volatile SIMOTION data "during power-up" provides you
with diagnostic information without HTML pages / TO alarm information.
Backing up during startup is particularly advisable for SIMOTION devices that cannot run or
have crashed.
Diagnostic data and non-volatile SIMOTION data are backed up
● Using a service selector switch or
● Using an INI file saved on the CF card
The procedure for each is described below.
SIMOTION D410
Commissioning Manual, 04/2014
The positions of the mode selector are not relevant (i.e. the operating mode set remains
unchanged).
The diagnostic data and non-volatile SIMOTION data can be created in STOP, STOPU,
and RUN modes.
The backup process is indicated on the SIMOTION D410 by the status LEDs as follows:
– Backup in progress: RUN/STOP LED flickers yellow
– Backup complete: RUN/STOP LED flickers green
7.2 Diagnostic data and non-volatile SIMOTION data
Diagnostics data
205