Maintenance and service
6.2 Replacing modules (spare part scenario)
6.2.2

Removing and replacing the SIMOTION D410

Overview
You must replace the entire SIMOTION D410 module.
NOTICE
Damage to property can occur
Installing or removing SIMOTION D410 with power connected can result in undefined states
in your system. Damage to property can occur in your automation solution as a result.
For this reason, only ever install or remove SIMOTION D410 with the power source
disconnected.
When configuring a system therefore always comply with the relevant standards and safety
regulations, which are mandatory in any case.
Danger to life due to live parts and other energy sources
Note that Power Modules with FSB performance rating or higher still carry a residual
intermediate voltage after shutdown.
Wait 10 minutes before you remove any screws.
Replacing defective modules
How to remove the SIMOTION D410 module:
1. Switch off the power supply.
2. Remove the CF card from the card slot.
3. Remove the connections for the power supply.
4. Disconnect the DRIVE-CLiQ connector from the device, and the PROFIBUS DP interface
5. If necessary, disconnect the digital I/O cable connectors at interface X121.
6. Disconnect the plug of any encoder connected to the X23 encoder interface.
7. Remove the SIMOTION D410 module from the Power Module or from the mounting panel,
How to install the new SIMOTION D410 module:
Note
Observe the information in the
connecting the SIMOTION D410 module.
168
DANGER
(X21) or PROFINET interface (X200 and X201) connectors.
depending on the type of assembly (see the "Installation" chapter in the
Manual).
SIMOTION D410 Manual, when installing, wiring and