Protective conductor connection and shield support

Shield contacts are only required if the system is connected to X521/X531.
Figure 8-15
The bending radii of the cables must be observed (see MOTION-CONNECT description).
NOTICE
Damage or faulty operation due to incorrect shielding or inadmissible cable lengths
If the correct shielding procedures or the permissible cable lengths are not observed, it can
cause damage or the machine may malfunction.
• Only use shielded cables.
• Do not exceed the cable lengths stated in the technical data.
8.1.4.8

Technical data

Table 8- 17
Technical data
6SL3055-0AA00-5CA2
Electronics power supply
Voltage
Current (without encoder system)
Current (with encoder system)
Power loss
Max. cable length
Encoder system power supply
Voltage
Current
Encoder frequency that can be evaluated
(f
)
encoder
AC Drive
Manual, (GH6), 07/2016, 6SL3097-4AL00-0BP5
Supplementary system components and encoder system integration
Protective conductor connection with M4 screw / 1.8 Nm
Shield connection terminal, Weidmüller company, type: KLBUE CO1, Article number:
1753311001
Shield support and PE conductor connection
Unit
V
DC
A
DC
A
DC
W
m
V
DC
A
DC
kHz
Value
24 (20.4 ... 28.8)
≤ 0.20
≤ 0.55
≤ 10
30
5 (with or without remote sense)
0.35
≤ 300
8.1 Sensor Modules
or V
- 1 V
1)
DC
319