X100 DRIVE-CLiQ interface

Table 7- 6
X100 DRIVE-CLiQ interface
Pin
1
2
3
4
5
6
7
8
A
B
Connector type
DRIVE-CLiQ socket
The blanking cover for the DRIVE-CLiQ port is included in the scope of delivery.
Blanking covers (50 pieces) Article No.: 6SL3066-4CA00-0AA0
7.3.2.5

X120 digital inputs (fail-safe)/EP terminal/temperature sensor

Table 7- 7
X120 fail-safe digital inputs/temperature sensor input
Terminal
1
2
3
4
5
6
7
8
9
10
11
12
Type: Spring-loaded terminal 1 (Page 371)
Max. cross-section that can be connected: 1.5 mm
DI: Digital input; DO: Digital output; F-DI: Fail-safe digital input
1)
Control of Power Modules chassis format:+Temp/-Temp deactivated, temperature input via terminal X41 of the Power
2)
Modules
Pure hardware delay
3)
AC Drive
Manual, (GH6), 07/2016, 6SL3097-4AL00-0BP5
Control Units, Control Unit Adapters and operating components
Signal name
TXP
TXN
RXP
Reserved, do not use
Reserved, do not use
RXN
Reserved, do not use
Reserved, do not use
+ (24 V)
M (0 V)
Designation
1)
+ Temp
2)
- Temp
2)
DI 16
F-DI 0
DI17+ / EP +24 V3
(Enable Pulses)
DI17- / EP M3
(Enable Pulses)
DI 18
F-DI 1
DI 19+
DI 19-
DI 20
F-DI 2
DI 21+
DI 21-
M1
2
7.3 Control Unit CU310-2 PN (PROFINET)
Technical data
Transmit data +
Transmit data -
Receive data +
-
-
Receive data -
-
-
Power supply
Electronic ground
Technical data
Temperature sensors: KTY84–1C130 / PT1000 / PTC
Measuring current via temperature sensor connection:
2 mA
Voltage: - 3 ... 30 V
Current consumption, typical: 6 mA at 24 VDC
Input delay (typ.):
2)
For "0" → "1": 50 μs
For "1" → "0": 150 μs
Level (including ripple):
High level: 15 ... 30 V
Low level: -3 ... 5 V
Electrical isolation:
M1: Reference potential for DO16, DI16, DI18 and
DI20
DI17-/DI19-/DI21-: Reference potential for
DI17/DI19/DI21