Chassis

6.2.1

Motor reactors

6.2.1.1

Description

Motor reactors reduce discharge currents which means that longer motor cables may be
used.
At the same time, the stress on the motor windings caused by rates of voltage rise (dv/dt) is
also diminished.
Preconditions
• Maximum ambient temperature:
• Maximum pulse frequency
• Maximum output frequency:
• Maximum current limit:
• Operating modes:
Support in STARTER
• From Version 2.4 and higher:
• From Version 2.5 and higher:
6.2.1.2

Safety instructions for motor reactors

Danger to life if the fundamental safety instructions and residual risks are not heeded
Failure to heed the fundamental safety instructions and residual risks in Chapter 1 can
result in accidents causing severe injuries or death.
• Follow the fundamental safety instructions.
• Consider the residual risks on the risk assessment.
AC Drive
Manual, (GH6), 07/2016, 6SL3097-4AL00-0BP5
WARNING
Motor-side power components
40 °C
4 kHz
120 Hz
2 x rated current
Vector control and U/f control
up to 1 motor reactor
up to 3 motor reactors