Siemens SINAMICS S120 Manual page 123

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Table 4- 26
Technical data of the PM240-2, FSE (200 V)
Line voltage 3 AC 200 ... 240 V ±10 %
Article No.
without integrated line filter
Output current
Rated current I
1)
n
Base load current I
H
for S6 duty (40 %) l
S6
Peak current l
max
Type rating
2)
based on I
n
based on I
H
Rated pulse frequency
Max. pulse frequency
Power loss
Cooling air requirement
Sound pressure level LpA (1 m)
24 V DC supply
for the Control Unit
Rated input current
4)
Resistance value of the external braking resistor
Max. cable length
to braking resistor
Line supply connection L1, L2, PE
Motor connection U2, V2, W2
DC-link connection, connection for braking resistor
DCP/R1, DCN, R2
Max. motor cable length
no EMC Category: shielded/unshielded
EMC Category C2: shielded
Weight
Rated current I
covers the load cycle for Low Overload.
1)
n
Rated power of a typical standard induction motor at 230 V 3 AC
2)
The values depend on the ambient temperature and the utilization level.
3)
The input current depends on the motor load and line impedance. The input currents apply for a load with the type rating
4)
(based on I
) for a line impedance corresponding to u
rated
AC Drive
Manual, (GH6), 07/2016, 6SL3097-4AL00-0BP5
3)
4.2 Blocksize Power Modules (PM240-2)
6SL3210–
1PC28-0UL0
A
80
A
68
A
96
A
136
kW
22
kW
18.5
kHz
4
kHz
16
kW
0.85
l/s
83
dB
44 ... 62
A
1.0
A
83
Ω
≥ 4.5
m
15
Screw-type terminal
Torx M8
Conductor cross section. 25 ... 70 mm
Tightening torque: 8.0 ... 10 Nm
Screw-type terminal
Torx M5
Conductor cross section: 10 ... 35 mm
Tightening torque: 2.5 ... 4.5 Nm
m
200/300
m
150
kg
26
= 1%.
k
Power Modules
6SL3210–
1PC31-1UL0
104
80
124
160
30
22
4
16
1.20
83
44 ... 62
1.0
107
≥ 4.5
15
2
2
26
123

Advertisement

Table of Contents
loading

Table of Contents