4.2 Blocksize Power Modules (PM240-2)
Line voltage 3-phase 380 ... 480 V AC ± 10%
Article No.
without integrated line filter
with integrated line filter
Rated current I
covers the load cycle for Low Overload.
1)
n
Rated power of a typical standard induction motor at 400 V 3 AC
2)
The input current depends on the motor load and line impedance. The input currents apply for a load with the type rating
3)
(based on I
) for a line impedance corresponding to u
rated
To observe the limit values of EN 61800-3 Category C2, for Power Modules PM240-2 with integrated line filter 50 m
4)
(shielded) is the max. motor cable length. A cable length up to 150 m is possible for C2 if you use an unfiltered Power
Module with an external line filter for Category C2 and a motor reactor.
Power loss in the cabinet: 0,045 kW. The remaining power loss is dissipated through the heat sink.
5)