Siemens SINAMICS S120 Manual page 35

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line power factor for line supply voltage 3 AC and
type rating
Devices FSA to FSC
Devices FSD to FSF
Electromagnetic compatibility
Interference immunity
Interference emission (second environment)
For devices with integrated radio interference
suppression filter
Standard
FSF devices with 690 V line supply voltage
For devices without integrated radio interference
suppression filter with optional external radio
interference filter for grounded line supplies
For devices without integrated radio interference
suppression filter for operation on IT line supplies
Interference emission (first environment)
Overvoltage category
Electronics power supply
implemented as PELV circuit according to EN 61800-
5-1
Rated short-circuit current (SCCR)
in conjunction with the specified fuses
in conjunction with the specified circuit breakers
Rated pulse frequency
For devices with 1/3 AC 200 V rated voltage
For devices with 3 AC 400 V rated voltage
and a type rating ≤ 90 kW based on I
and a type rating ≥ 110 kW based on I
For devices with 3 AC 690 V line voltage
Output voltage
Output frequency
When using a motor holding brake, possibly restricted voltage tolerances (24 V ±10 %) must be taken into account.
1)
Higher output frequencies available on request. In this case, an additional license is required.
2)
AC Drive
Manual, (GH6), 07/2016, 6SL3097-4AL00-0BP5
Active power factor (cos φ1): > 0.96
Power factor (λ): > 0.70 ... 0.85
Active power factor (cos φ1): > 0.98 ... 0.99
Power factor (λ): > 0.90 ... 0.92
All PM240-2 Power Modules are suitable for use in both the first
and second environments.
According to EN 61800-3
Category C2
Category C3
Category C2 (recommended for operation in conjunction with a
residual current protective device (RCD))
Category C4
According to EN 61800-3
Can be used in the "First environment Category C2" when taking
into account the additional secondary conditions for use listed in
Chapter "Notes regarding electromagnetic compatibility (EMC)
(Page 351)".
III acc. to EN 61800-5-1
24 V DC -15 / +20 %
through the electronics
≤ 100 kA
see information regarding UL
4 kHz
4 kHz
n
2 kHz
n
2 kHz
Approx. 0.95 • line voltage (maximum value)
approx. 0.74 • line voltage at 1 AC 200 V
0 ... 550 Hz, dependencies on the control mode and pulse
frequency must be taken into account
, ground = negative polarity grounded
1)
2)
System overview
2.5 System data
35

Advertisement

Table of Contents
loading

Table of Contents