Operation
Mechanical environmental conditions
Long-term storage
Transport
Operation
Vibration test in operation
Shock test in operation
Installation altitude
Operation
Permissible cooling medium
temperature (air) and installation
altitude in operation
Product packaging (storage packaging) is individual packaging for storage - and does not satisfy the requirements for
1)
transport. As a consequence, product packaging is therefore not suitable for shipping.
Transport packaging is either packaging that is directly suitable for transport - or secondary packaging, which together
2)
with the product packaging, satisfies the requirements for transport.
Table 2- 8
Certificates
Declarations of Conformity
Approvals
AC Drive
Manual, (GH6), 07/2016, 6SL3097-4AL00-0BP5
Class 3K3 according to EN 60721-3-3
Temperature: 0 ... +40 °C without derating
> 40 ... +55 °C with reduction of the output current by 2.67 % pro °C
Relative humidity: 5 ... 90 % no condensation
Oil mist, salt mist, ice formation, condensation, dripping water, spraying water,
splashing water and water jets are not permitted
Class 1M2 according to EN 60721-3-1, in product packaging
Class 2M2 according to EN 60721-3-2, in transport packaging
Class 3M1 according to EN 60721-3-3
According to IEC 60068-2-6 test Fc (sinusoidal)
10 ... 57 Hz: 0.075 mm deflection amplitude
57 ... 150 Hz: 1g acceleration amplitude
10 frequency cycles per axis
According to IEC 60068-2-27 test Ea (half-sine)
10 g peak acceleration
20 ms duration
3 shocks in all three axes in both directions
0 ... 1000 m above sea level without derating
> 1000 ... 4000 m
Reduction of the output current by 10 % per 1000 meters, or
Reduction of the ambient temperature by 5°C per 1000 meters
> 2000 ... 4000 m
Operation on supply systems with grounded neutral, or
Operation on an isolating transformer with secondary grounded neutral point
0 °C ... +40 °C and an installation altitude of up to 1000 m without derating,
> 40 °C to +55 °C see the characteristic for current derating.
Installation altitude >1000 m up to 4000 m see characteristic for current derating or
reduction of the ambient temperature by 3.5°°C per 500 m.
CE (Low Voltage, EMC and Machinery Directives)
cULus, cURus
Testing by UL (Underwriters Laboratories (www.ul.com)) according to UL
and CSA standards