Service and maintenance
11.3 Service and maintenance for Chassis format components
Cable and screw terminals
Cable and screw terminals must be checked regularly to ensure that they are secure in
position, and if necessary, retightened. Cabling must be checked for defects. Defective parts
must be replaced immediately.
Note
The actual intervals at which maintenance procedures are to be performed depend on the
installation conditions (cabinet environment) and the operating conditions.
Siemens offers its customers support in the form of a service contract. For further details,
contact your regional office or sales office.
11.3.1

Maintenance

Servicing involves activities and procedures for maintaining and restoring the operating
condition of the devices.
Required tools
The following tools are required for replacing components:
● Standard set of tools with screwdrivers, screw wrenches, socket wrenches, etc.
● Torque wrenches 1.5 Nm up to 100 Nm
● 600 mm extension for socket wrenches
Tightening torques for screw connections
The following tightening torques apply when tightening current-conducting connections (DC
link connections, motor connections, busbars, lugs) and other connections (ground
connections, protective conductor connections, steel threaded connections).
Table 11- 1
388
Tightening torques for screw connections
Thread
Ground connections, protective
conductor connections, steel
M3
M4
M5
M6
M8
M10
M12
threaded connections
1.3 Nm
3 Nm
6 Nm
10 Nm
25 Nm
50 Nm
88 Nm
Manual, (GH6), 07/2016, 6SL3097-4AL00-0BP5
Aluminum threaded connections,
plastic, busbars, lugs
0.8 Nm
1.8 Nm
3 Nm
6 Nm
13 Nm
25 Nm
50 Nm