Chassis Line Reactors; Line Connection Variants; Operation On Different Line System Configurations - Siemens SINAMICS S120 Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Mains connection and line-side power components

3.9 Line connection variants

3.8.6.2

Chassis line reactors

Table 3- 27
Technical data, Chassis line reactors
Article number
Suitable for
Power Module
Rated current of the
Power Module
Rated voltage
I
thmax
Power loss
Line/load connection
1U1, 1V1, 1W1, 1U2,
1V2, 1W2
PE connection
Degree of protection
Weight
3.9
Line connection variants
3.9.1

Operation on different line system configurations

The Power Modules are designed for the following power distribution systems according to
IEC 60364-1.
Note
• At an installation altitude of more than 1000 m, observe the information in Chapter
Derating (Page 40).
74
6SL3000-
0CE32-3AA0
6SL3310-
1TE32-1AA.
A
210
V
380 V 3 AC - 10 % ... 480 V 3 AC + 10 % (-15 % < 1 min), 47 ... 63 Hz
A
224
kW
0.274
M10
connecting
lugs
M6 screw
IP00
kg
24.5
0CE32-8AA0
0CE33-3AA0
1TE32-6AA.
1TE33-1AA.
260
310
278
331
0.247
0.267
M10
M10
connecting
connecting
lugs
lugs
M6 screw
M6 screw
IP00
IP00
26
27.8
Manual, (GH6), 07/2016, 6SL3097-4AL00-0BP5
0CE35-1AA0
0CE35-1AA0
1TE33-8AA.
1TE35-0AA.
380
490
508
508
0.365
0.365
M12
M12
connecting
connecting
lugs
lugs
M6 screw
M6 screw
IP00
IP00
38
38
AC Drive