Optimize the drive.
11.2 Frequency response measurements
Measurement
The measurement sequence is divided into the following steps:
1. Setting the traverse range monitoring and the enable logic.
2. Selecting the measurement type
3. Setting the parameters, softkey "Measuring parameters"
4. Displaying the measurement results, softkey "Display"
Figure 11-1
Measuring parameters
● Amplitude
● Bandwidth
192
Current controller
Magnitude of the test signal amplitude. Given in percent of the peak torque. Values from
1% to 5% are suitable.
The frequency range analyzed with the measurement.
The bandwidth depends on the current controller sampling time.
Example:
125 μs current controller sampling time, set bandwidth 4000 Hz
Commissioning Manual, 07/2007, 6FC5397-2AP10-3BA0
IBN CNC: NCK, PLC, drive