Parameters

3.7 Main Menu - Analog In/Out - Group 6

Parameter group for setting up the analog I/O configu-
ration and the digital output. The frequency converter
provides 2 analog inputs:
Terminal 53.
Terminal 54.
The analog inputs can be freely allocated to either voltage
(0–10 V) or current input (0/4–20 mA).
3.7.1 6-0* Analog I/O Mode
6-00 Live Zero Timeout Time
Range:
Function:
10 s
[1 - 99 s]
Enter the timeout time.
*
6-01 Live Zero Timeout Function
Option:
Function:
Select the timeout function. The function set
in parameter 6-01 Live Zero Timeout Function is
activated if the input signal on terminal 53 or
54 is below 50% of the value in
parameter 6-10 Terminal 53 Low Voltage,
parameter 6-12 Terminal 53 Low Current,
parameter 6-20 Terminal 54 Low Voltage, or
parameter 6-22 Terminal 54 Low Current for a
time period defined in parameter 6-00 Live
Zero Timeout Time.
[0]
Off
*
[1]
Freeze
output
[2]
Stop
[3]
Jogging
[4]
Max. speed
[5]
Stop and
trip
BAS-SVP16B-EN
Programming Guide
Illustration 3.10 Live Zero Timeout Function
6-02 Fire Mode Live Zero Timeout Function
Option:
[0]
Off
*
[1]
Freeze
output
[2]
Stop
[3]
Jogging
[4]
Max. speed
3.7.2 6-1* Analog Input 53
Parameters for configuring the scaling and limits for analog
input 53 (terminal 53).
6-10 Terminal 53 Low Voltage
Range:
0.07 V
*
6-11 Terminal 53 High Voltage
Range:
10 V
*
02/2017 All rights reserved.
Function:
Select the timeout function when the fire
mode is active. The function set in this
parameter is activated if the input signal on
analog inputs is below 50% of the low value
for a time period defined in
parameter 6-00 Live Zero Timeout Time.
Function:
[0 - 10
Enter the voltage (V) that corresponds to
V]
parameter 6-14 Terminal 53 Low Ref./Feedb.
Value. To activate parameter 6-01 Live Zero
Timeout Function, set the value at >1 V.
Function:
[0 - 10 V] Enter the voltage (V) that corresponds to the
high reference value (set in
parameter 6-15 Terminal 53 High Ref./Feedb.
Value).
3
3
55