Parameters
8-43 PCD Read Configuration
Different parameters can be assigned to PCD 3–10 of the PPOs
(the number of PCDs depends on the PPO type). PCD 3–10 hold
the actual data value of the selected parameters.
Option:
3
3
[34]
3.8.4 8-5* Digital/Bus
Parameters for configuring the control word digital/bus
merging.
8-50 Coasting Select
Option:
[0]
Digital
input
[1]
Bus
[2]
Logic
AND
[3]
Logic OR Activates coast via the serial communication port
*
8-51 Quick Stop Select
Option:
[0]
Digital
input
[1]
Bus
[2]
Logic
AND
[3]
Logic OR Activates quick stop via the serial communi-
*
62
[1694] Ext. Status Word
Function:
NOTICE
This parameter is active only when
parameter 8-01 Control Site is set to [0]
Digital and control word.
Select control of the coasting function via the
terminals (digital input) and/or via the bus.
Activates coast via a digital input.
Activates coast via the serial communication
port.
Activates coast via the fieldbus/serial communi-
cation port, and via 1 of the digital inputs.
or via 1 of the digital inputs.
Function:
NOTICE
This parameter is active only when
parameter 8-01 Control Site is set to [0]
Digital and control word.
Select control of the quick stop function via the
terminals (digital input) and/or via the bus.
Activates quick stop via a digital input.
Activates quick stop via the serial communi-
cation port.
Activates quick stop via the serial communi-
cation port, and via 1 of the digital inputs.
cation port or via 1 of the digital inputs.
TR150 and TR170
8-52 DC Brake Select
Option:
Function:
[0] Digital
input
[1] Bus
[2] Logic
AND
[3] Logic OR
8-53 Start Select
Option:
[0]
Digital
input
[1]
Bus
[2]
Logic
AND
[3]
Logic
*
OR
8-54 Reversing Select
Option:
[0]
Digital
*
input
[1]
Bus
02/2017 All rights reserved.
Function:
NOTICE
This parameter is active only when
parameter 8-01 Control Site is set to [0]
Digital and control word.
Select control of the DC brake via the terminals
(digital input).
Activates DC brake via a digital input.
Activates DC brake via the serial communication
port.
Activates DC brake via the serial communication
port, and via 1 of the digital inputs.
Activates DC brake via the serial communication
port or via 1 of the digital inputs.
Function:
NOTICE
This parameter is active only when
parameter 8-01 Control Site is set to [0]
Digital and control word.
Select control of the frequency converter start
function via the terminals (digital input).
Activates a start command via a digital input.
Activates a start command via the serial
communication port or fieldbus options.
Activates a start command via the serial
communication port, and via 1 of the digital
inputs.
Activates a start command via the serial
communication port or via 1 of the digital inputs.
Function:
NOTICE
This parameter is active only when
parameter 8-01 Control Site is set to [0]
Digital and control word.
Select control of the frequency converter reverse
function via the terminals (digital input) and/or
via the serial communication port.
Activates a reverse command via a digital input.
Activates a reverse command via the serial
communication port.