3-16 Reference 2 Source
Option:
3
3
[0]
No function
[1]
Analog Input
53
[2]
Analog Input
*
54
[7]
Pulse input 29
[11] Local bus
reference
3-17 Reference 3 Source
Option:
[0]
No function
[1]
Analog Input
53
[2]
Analog Input
54
[7]
Pulse input 29
[11]
Local bus
*
reference
3.4.3 3-4* Ramp 1
Configure the ramp time parameters, for each of the 2
ramps (parameter group 3-4* Ramp 1 and parameter group
3-5* Ramp 2). The ramp time is preset to the minimum
value of 10 ms for all power sizes.
Illustration 3.6 Ramps
42
TR150 and TR170
Function:
The sum of these reference signals defines
the actual reference. See also
parameter 1-93 Thermistor Source.
Function:
Select the reference input to be used for
rd
the 3
reference signal.
Parameter 3-15 Reference 1 Source,
parameter 3-16 Reference 2 Source, and
parameter 3-17 Reference 3 Source define
up to 3 different reference signals. The
sum of these reference signals defines the
actual reference.
02/2017 All rights reserved.
3-41 Ramp 1 Ramp Up Time
Range:
Function:
Size
[0.05 -
Enter acceleration time from 0 Hz to
related
3600 s]
parameter 1-23 Motor Frequency if
*
asynchronous motor is selected. Enter
acceleration time from 0 RPM, to
parameter 1-25 Motor Nominal Speed if PM
motor is selected. Select a ramp-up time
such that the output current does not
exceed the current limit in
parameter 4-18 Current Limit during ramping.
See ramp-down time in
parameter 3-42 Ramp 1 Ramp Down Time.
3-42 Ramp 1 Ramp Down Time
Range:
Function:
Size
[0.05 -
If asynchronous motor is selected, enter
related
3600 s]
deceleration time from
*
parameter 1-23 Motor Frequency to 0 Hz. If
PM motor is selected, enter deceleration
time from parameter 1-25 Motor Nominal
Speed to 0 RPM. Select a ramp-down time
to avoid tripping on overvoltage in the
DC-link.
3.4.4 3-5* Ramp 2
This parameter group configures ramp 2 parameters.
3-51 Ramp 2 Ramp Up Time
Range:
Function:
Size
[0.05 -
If asynchronous motor is selected, enter
related
3600 s]
acceleration time from 0 Hz to
*
parameter 1-23 Motor Frequency. If PM
motor is selected, enter acceleration time
from 0 RPM to parameter 1-25 Motor
Nominal Speed. Select a ramp-up time such
that the output current does not exceed
the current limit in parameter 4-18 Current
Limit during ramping up.
3-52 Ramp 2 Ramp Down Time
Range:
Function:
Size
[0.05 -
Enter deceleration time from
related
3600 s]
parameter 1-25 Motor Nominal Speed to
*
0 RPM. Select a ramp-down time such
that the output current does not exceed
the current limit in
parameter 4-18 Current Limit during
ramping down.
BAS-SVP16B-EN