Parameters
13-52 SL Controller Action
Array [20]
Option:
[25]
Qstop
3
3
[26]
DC Brake
[27]
Coast
[28]
Freeze output
[29]
Start timer 0
[30]
Start timer 1
[31]
Start timer 2
[32]
Set digital out A
low
[33]
Set digital out B
low
[34]
Set digital out C
low
[35]
Set digital out D
low
[38]
Set digital out A
high
[39]
Set digital out B
high
[40]
Set digital out C
high
[41]
Set digital out D
high
[60]
Reset Counter A
[61]
Reset Counter B
[70]
Start Timer 3
[71]
Start Timer 4
[72]
Start Timer 5
[73]
Start Timer 6
[74]
Start Timer 7
[100] Reset Alarm
72
TR150 and TR170
Function:
Issues a quick stop command to the
frequency converter.
Issues a DC stop command to the
frequency converter.
The frequency converter coasts
immediately. All stop commands
including the coast command stop the
SLC.
Freezes the output frequency of the
frequency converter.
Starts timer 0, see parameter 13-20 SL
Controller Timer for further description.
Starts timer 1, see parameter 13-20 SL
Controller Timer for further description.
Starts timer 2, see parameter 13-20 SL
Controller Timer for further description.
Any output with digital output 1
selected is low (off).
Any output with digital output 2
selected is low (off).
Any output with digital output 3
selected is low (off).
Any output with digital output 4
selected is low (off).
Any output with digital output 1
selected is high (closed).
Any output with digital output 2
selected is high (closed).
Any output with digital output 3
selected is high (closed).
Any output with digital output 4
selected is high (closed).
Resets counter A to 0.
Resets counter B to 0.
Starts timer 3, see parameter 13-20 SL
Controller Timer for further description.
Starts timer 4, see parameter 13-20 SL
Controller Timer for further description.
Starts timer 5, see parameter 13-20 SL
Controller Timer for further description.
Starts timer 6, see parameter 13-20 SL
Controller Timer for further description.
Starts timer 7, see parameter 13-20 SL
Controller Timer for further description.
Reset the alarm.
02/2017 All rights reserved.
BAS-SVP16B-EN

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tr170

Table of Contents