Parameters
8-54 Reversing Select
Option:
Function:
[2]
Logic
Activates a reverse command via the serial
AND
communication port, and via 1 of the digital
inputs.
[3]
Logic
Activates a reverse command via the serial
OR
communication port or via 1 of the digital inputs.
8-55 Set-up Select
Option:
Function:
NOTICE
This parameter is active only when
parameter 8-01 Control Site is set to [0]
Digital and control word.
Select control of the frequency converter set-up
selection via the terminals (digital input) and/or
via the serial communication port.
[0]
Digital
Activates the set-up selection via a digital input.
input
[1]
Bus
Activates the set-up selection via the serial
communication port.
[2]
Logic
Activates the set-up selection via the serial
AND
communication port, and via 1 of the digital
inputs.
[3]
Logic
Activate the set-up selection via the serial
*
OR
communication port or via 1 of the digital inputs.
8-56 Preset Reference Select
Option:
Function:
Select control of the frequency converter preset
reference selection via the terminals (digital
input) and/or via the serial communication port.
[0]
Digital
Activates the preset reference selection via a
input
digital input.
[1]
Bus
Activates the preset reference selection via the
serial communication port.
[2]
Logic
Activates the preset reference selection via the
AND
serial communication port, and via 1 of the
digital inputs.
[3]
Logic OR
Activates the preset reference selection via the
*
serial communication port or via 1 of the digital
inputs.
3.8.5 8-7* BACnet
8-70 BACnet Device Instance
Range:
Function:
1
[0 - 4194303 ] Enter a unique ID number for the BACnet
*
device.
BAS-SVP16B-EN
Programming Guide
8-72 MS/TP Max Masters
Range:
127
[0 - 127 ] Define the address of the master, which holds
*
8-73 MS/TP Max Info Frames
Range:
1
[1 - 65534 ] Define how many info/data frames the device
*
8-74 "I am" Service
Option:
[0]
Send at
*
power-up
[1]
Continuously
8-75 Intialisation Password
Range:
admin
*
8-79 Protocol Firmware version
Array[5]
Range:
Size
related
*
3.8.6 8-8* FC Port Diagnostics
These parameters are used for monitoring the bus
communication via the Drive port.
8-80 Bus Message Count
Range:
0
[0 - 4294967295 ] This parameter shows the number of
*
8-81 Bus Error Count
Range:
0
[0 - 4294967295 ] This parameter shows the number of
*
8-82 Slave Messages Rcvd
Range:
0
[0 - 4294967295 ] This parameter shows the number of
*
02/2017 All rights reserved.
Function:
the highest address in this network. Decreasing
this value optimizes polling for the token.
Function:
is allowed to send while holding the token.
Function:
Select when the device should send the I-
Am service message only at power-up.
Select when the device should send the I-
Am service message continuously with an
interval of approximately 1 minute.
Function:
[1 - 1 ] Enter the password needed for execution of
Drive Re-initialization from BACnet.
Function:
[0 -
Firmware revision of frequency
65535 ]
converter is in index 0, Modbus is in
index 1, Metasys N2 is in index 2, FLN
is in index 3, BACnet is in index 4.
Function:
valid telegrams detected on the bus.
Function:
telegrams with faults (for example, CRC
fault), detected on the bus.
Function:
valid telegrams addressed to the slave,
sent by the frequency converter.
3