Setpoint Menu - Trane Picco R3206A Manual

Hide thumbs Also See for Picco R3206A:
Table of Contents

Advertisement

5. USER INTERFACE - CONTROLLER
Select the operating mode and manually reset any alarms.
Each time you press the key you have the following sequence:
OFF -> COOL -> HEAT -> OFF
If DHW is enabled, the sequence is the following:
OFF -> COOL -> COOL+SAN -> HEAT -> HEAT+SAN -> OFF
While setting the parameters, this key has the function of sending BACK by one level.
Grants access to the parameter setting menu and allows you to set the summer, winter and sanitary setpoint.
UP key. In the parameter setting mode, it allows you to move to a higher menu or to increase the parameter value when in "edit"
mode.
DOWN key. In the parameter setting mode, it allows you to move to a lower menu or to decrease the parameter value when in
"edit" mode.
5.1 MENU
The following are the main features for navigating the menus, especially describing functions which are not obvious. The main menu has the
following items:
MENU
Setpoint
Probes
Alarms
Digital input
Parameters
Password
Hours of operations
USB
Versione Firmware
Alarm log
The PSS menu is accessed to enter the service password and to enable access with a higher user permission. When you have exited the menus,
the password must be entered once again to re-enter.
5.2 SETPOINT MENU
The various setpoints can be viewed and edited.
SETPOINT
Coo
Hea
*San
Coo2
Hea2
San2
**rCoo
LABEL
PASSWORD LEVEL
Set
User
tP
Installer
Err
User
Id
Installer
Par
Installer
PSS
User
oHr
Installer
USb
Installer
Fir
Installer
Hist
Installer
DESCRIPTION
First Summer setpoint
First Winter setpoint
Sanitary setpoint
Second Summer setpoint
Second Winter setpoint
Second Sanitary setpoint
Mixing valve Summer setpoint
Picco R32
Heat pumps inverter air/water with axial fans
OTHER CONDITIONS
Not accessible if connected to Hi-T2
---
Only if active alarms
---
---
---
---
Only with pen drive with relevant update files
Version, Revision and Sub
Only if the log contains data
UNIT
DEFAULT
°C
7.0
°C
45.0
°C
48.0
°C
18.0
°C
35.0
°C
35.0
°C
15.0
RANGE
5 ÷ Co2
25 ÷ 60
25 ÷ 60
Coo ÷ 25
25 ÷ Hea
25 ÷ Hea
0.0 ÷ 80