Parameters
6-26 Terminal 54 Filter Time Constant
Range:
Function:
dampening, but also increases the time
delay through the filter.
6-29 Terminal 54 mode
Option:
Function:
Select if terminal 54 is used for current
input or voltage input.
[0]
Current mode
[1]
Voltage mode
*
3.7.4 6-7* Analog/Digital Output 45
Parameters for configuring the scaling and limits for
analog/digital output terminal 45. Analog outputs are
current outputs: 0/4–20 mA. Resolution on analog output
is 12 bit. Analog output terminals can also be set up as
digital output.
6-70 Terminal 45 Mode
Option:
Function:
Set terminal 45 to act as analog output or
as digital output.
[0]
0-20 mA
*
[1]
4-20 mA
[2]
Digital Output
6-71 Terminal 45 Analog Output
Option:
Function:
Select the function of terminal 45 as an
analog current output. See also
parameter 6-70 Terminal 45 Mode.
[0]
No operation
*
[100] Output
0–100 Hz
frequency
[101] Reference
Min
Ref.
[102] Feedback
Min
–Max
FB
[103] Motor Current
0–I
max
[106] Power
0–P
nom
[139] Bus Control
0–100%
6-72 Terminal 45 Digital Output
Option:
[0]
No operation
*
BAS-SVP16B-EN
Programming Guide
–Max
Ref.
FB
Function:
Select the function of
terminal 45 as a digital
current output. See also
parameter 6-70 Terminal 45
Mode. See
parameter 5-40 Function
Relay for description of the
options.
02/2017 All rights reserved.
6-72 Terminal 45 Digital Output
Option:
[1]
Control Ready
[2]
Drive ready
[3]
Drive ready/remote control
[4]
Standby / no warning
[5]
Drive running
[6]
Running / no warning
[7]
Run in range/no warning
[8]
Run on ref/no warning
[9]
Alarm
[10]
Alarm or warning
[12]
Out of current range
[13]
Below current, low
[14]
Above current, high
[16]
Below speed, low
[17]
Above speed, high
[19]
Below feedback, low
[20]
Above feedback, high
[21]
Thermal warning
[22]
Ready, no thermal warning
[23]
Remote, ready, no thermal
warning
[24]
Ready, Voltage OK
[25]
Reverse
[26]
Bus OK
[35]
External Interlock
[36]
Control word bit 11
[37]
Control word bit 12
[41]
Below reference, low
[42]
Above ref, high
[45]
Bus Control
[60]
Comparator 0
[61]
Comparator 1
[62]
Comparator 2
[63]
Comparator 3
[64]
Comparator 4
[65]
Comparator 5
[70]
Logic rule 0
[71]
Logic rule 1
[72]
Logic rule 2
[73]
Logic rule 3
[74]
Logic rule 4
[75]
Logic rule 5
[80]
SL digital output A
[81]
SL digital output B
[82]
SL digital output C
[83]
SL digital output D
[160] No alarm
[161] Running reverse
[165] Local ref. active
[166] Remote ref. active
[167] Start command activ
[168] Drive in hand mode
Function:
3
57
3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tr170

Table of Contents