Parameters
6-92 Terminal 42 Digital Output
Option:
[25]
Reverse
[26]
Bus OK
[35]
External Interlock
[36]
Control word bit 11
[37]
Control word bit 12
[41]
Below reference, low
[42]
Above ref, high
[45]
Bus Control
[60]
Comparator 0
[61]
Comparator 1
[62]
Comparator 2
[63]
Comparator 3
[64]
Comparator 4
[65]
Comparator 5
[70]
Logic rule 0
[71]
Logic rule 1
[72]
Logic rule 2
[73]
Logic rule 3
[74]
Logic rule 4
[75]
Logic rule 5
[80]
SL digital output A
[81]
SL digital output B
[82]
SL digital output C
[83]
SL digital output D
[160] No alarm
[161] Running reverse
[165] Local ref. active
[166] Remote ref. active
[167] Start command activ
[168] Drive in hand mode
[169] Drive in auto mode
[190] No-Flow
[193] Sleep Mode
[194] Broken Belt Function
[196] Fire Mode
[198] Drive Bypass
6-93 Terminal 42 Output Min Scale
Range:
Function:
0 %
[0 -
Scale for the minimum output (0 mA or 4 mA)
*
200 %]
of the analog signal at terminal 42. Set the
value to be the percentage of the full range
of the variable selected in parameter 6–
91 Terminal 42 Analog Output.
BAS-SVP16B-EN
Programming Guide
Function:
02/2017 All rights reserved.
6-94 Terminal 42 Output Max Scale
Range:
Function:
100
[0 -
Scale for the maximum output (20 mA) of the
%
200 %]
scaling at terminal 42. Set the value to be the
*
percentage of the full range of the variable
selected in parameter 6–91 Terminal 42 Analog
Output.
Illustration 3.12 Output Maximum Scale
6-96 Terminal 42 Output Bus Control
Range:
Function:
0
[0 - 16384 ] Hold the analog output at terminal 42 if
*
controlled by bus.
3
3
59