Parameters
13-40 Logic Rule Boolean 1
Array [6]
Option:
Function:
[22] Comparator 0
Use the result of comparator 0 in the
logic rule.
[23] Comparator 1
Use the result of comparator 1 in the
logic rule.
[24] Comparator 2
Use the result of comparator 2 in the
logic rule.
[25] Comparator 3
Use the result of comparator 3 in the
logic rule.
[26] Logic rule 0
Use the result of logic rule 0 in the logic
rule.
[27] Logic rule 1
Use the result of logic rule 1 in the logic
rule.
[28] Logic rule 2
Use the result of logic rule 2 in the logic
rule.
[29] Logic rule 3
Use the result of logic rule 3 in the logic
rule.
[30] SL Time-out 0
Use the result of timer 0 in the logic rule.
[31] SL Time-out 1
Use the result of timer 1 in the logic rule.
[32] SL Time-out 2
Use the result of timer 2 in the logic rule.
[33] Digital input
Use the value of DI18 in the logic rule
DI18
(High = true).
[34] Digital input
Use the value of DI19 in the logic rule
DI19
(High = true).
[35] Digital input
Use the value of DI27 in the logic rule
DI27
(High = true).
[36] Digital input
Use the value of DI29 in the logic rule
DI29
(High = true).
[39] Start command
This logic rule is true if the frequency
converter is started by any means (either
via digital input, or other).
[40] Drive stopped
This logic rule is true if the frequency
converter is stopped or coasted by any
means (either via digital input, or other).
[42] Auto Reset Trip
This logic rule is true if the frequency
converter is tripped (but not trip-locked)
and an automatic reset is issued.
[50] Comparator 4
Use the result of comparator 4 in the
logic rule.
[51] Comparator 5
Use the result of comparator 5 in the
logic rule.
[60] Logic rule 4
Use the result of logic rule 4 in the logic
rule.
[61] Logic rule 5
Use the result of logic rule 5 in the logic
rule.
[70] SL Time-out 3
Use the result of timer 3 in the logic rule.
BAS-SVP16B-EN
Programming Guide
13-40 Logic Rule Boolean 1
Array [6]
Option:
[71] SL Time-out 4
[72] SL Time-out 5
[73] SL Time-out 6
[74] SL Time-out 7
[83] Broken Belt
13-41 Logic Rule Operator 1
Option:
[0]
*
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
13-42 Logic Rule Boolean 2
Array [6]
Option:
[0]
False
*
[1]
True
[2]
Running
[3]
In range
[4]
On reference
[7]
Out of current range
[8]
Below I low
[9]
Above I high
[16] Thermal warning
[17] Mains out of range
[18] Reversing
[19] Warning
[20] Alarm (trip)
[21] Alarm (trip lock)
[22] Comparator 0
[23] Comparator 1
[24] Comparator 2
[25] Comparator 3
[26] Logic rule 0
[27] Logic rule 1
[28] Logic rule 2
02/2017 All rights reserved.
Function:
Use the result of timer 4 in the logic rule.
Use the result of timer 5 in the logic rule.
Use the result of timer 6 in the logic rule.
Use the result of timer 7 in the logic rule.
A broken-belt condition has been
detected. Enable this function in
parameter 22-60 Broken Belt Function.
Disabled
AND
OR
AND NOT
OR NOT
NOT AND
NOT OR
NOT AND NOT
NOT OR NOT
Function:
nd
Select the 2
boolean (true or false)
input for the selected logic rule.
See parameter 13-40 Logic Rule
Boolean 1 for further descriptions of
options and their functions.
3
Function: